標題: | A model to predict total chlorine residue in the cooling seawater of a power plant using iodine colorimetric method | 作者: | Wang, J.-T. Chen, M.-H. Lee, H.-J. Chang, W.-B. Chen, C.-C. Pai, S.-C. Meng, P.-J. SU-CHENG PAI |
關鍵字: | Anti-fouling agent; Cooling water; Power plant; Total residual oxidant | 公開日期: | 2008 | 卷: | 9 | 期: | 4 | 起(迄)頁: | 542-553 | 來源出版物: | International Journal of Molecular Sciences | 摘要: | A model experiment monitoring the fate of total residue oxidant (TRO) in water at a constant temperature and salinity indicated that it decayed exponentially with time, and with TRO decaying faster in seawater than in distilled water. The reduction of TRO by temperature (°K) was found to fit a curvilinear relationship in distilled water (r 2 = 0.997) and a linear relationship in seawater (r 2 = 0.996). Based on the decay rate, flow rate, and the length of cooling water flowing through at a given temperature, the TRO level in the cooling water of a power plant could be estimated using the equation developed in this study. This predictive model would provide a benchmark for power plant operators to adjust the addition of chlorine to levels necessary to control bio-fouling of cooling water intake pipelines, but without irritating ambient marine organisms. © 2008 by MDPI. |
URI: | http://www.scopus.com/inward/record.url?eid=2-s2.0-43049131464&partnerID=MN8TOARS http://scholars.lib.ntu.edu.tw/handle/123456789/339233 |
DOI: | 10.3390/ijms9040542 | SDG/關鍵字: | chlorine; cooling water; sea water; article; biofouling; colorimetry; electric power plant; flow rate; marine species; mathematical model; salinity; temperature |