  4. Development of the louver electrostatic precipitator and the characteristics of particle generation by corona discharge
 
  • Details

Development of the louver electrostatic precipitator and the characteristics of particle generation by corona discharge

Date Issued
2012
Date
2012
Author(s)
Lin, Chih-Wei
URI
http://ntur.lib.ntu.edu.tw//handle/246246/257765
Abstract
An air conditioner is used to increase the occupants’ comfort by adjusting the indoor air temperature, but it is a major part of energy consumption. We can achieve equivalent or superior results by using general ventilation but drawbacks may include the incursion of outdoor air pollutants and an increase in radiant energy from sunlight into the home. This study designs a low-cost, practical, louver-window-type, electrostatic precipitator that can reduce pollutants entering the indoor space and shade the indoor area, while permitting increased ventilation in a home or small office environment. We also demonstrated that an electrostatic precipitator, originally designed for dust collection, could become an efficient nanoparticle generator under specific operating conditions. This unique feature was utilized in the present study to develop a nanoparticle generator based on corona discharge. A lab-scale, adjustable, wire-plate positive louver ESP and a wire-plate corona discharger were built for measuring particle penetration, energy quality, ozone concentration and particle emission. Environmental contaminants were removed by HEPA filter, active charcoal and silica gel. Gold, tungsten, molybdenum, and stainless steel were used as the electrode to study the material dependency. Gas temperature was controlled by a feedback heater. A positive direct current power supply was employed to energize the corona discharger. A scanning mobility particle sizer with a nano differential mobility analyzer was employed to measure the aerosol number concentration and size distribution. Ozone concentration was monitored by using an ozone analyzer. The sampling locations of SMPS and ozone analyzer were 20 and 15 cm downstream the corona discharger, respectively. The major operating parameters included louver angle, electrode diameter, electrode spacing, electrode material, air velocity, air temperature, applied voltage and current. The results showed that the louver adjustment significantly affected the ESP performance. The discharge wire should be positioned in the middle to provide optimal ESP performance, although moving around the electrode did not significantly change the energy consumption and ozone generation. The collection plates with excessive length were proven to be ineffective. The wire-to-plate distance decreased with increasing louver angle. The louver adjustments resulted in changes of the effective collection area, electric field strength and air velocity. The field strength should be as low as possible to obtain a high energy quality index. For a given energy consumption, the energy quality index was not significantly affected by the louver angle. This phenomenon was due to a trade-off between the electric field strength and the effective collection area. Therefore, all aerosol penetration curves showed within a narrow band. The air temperature appeared to have a strong effect on ESP nanoparticle generation. At temperature above 37°C and flow rate below 9 L/min, the nanoparticle penetration of ESP exceeded 100%, indicating that the ESP was generating aerosol particles. Sputtering on the corona discharger appeared to be the key mechanism of aerosol generation. Particles were generated as soon as the ESP was on set. The ozone concentration increased with increasing corona current. The ESP reached a maximum number concentration at the electric field strength of 4.8 kv/cm when the air flow and temperature were fixed at 6 L/min and 40°C, respectively. The particle size ranged from 5 to 40 nm. Elementary components of the discharge wire were detected on the filter samples collected downstream the ESP and ground plates, indicating that nanoparticles were generated from the discharge wire. The ESP transit to a nanoparticle generator when it could not efficiently capture the particles generated from itself. The maximum aerosol concentration occurred when the electric field strength was around 8.2, 9.8, and 11.2 kV for electrode diameter of 0.1, 0.2 and 0.3 mm, respectively. The smaller discharge electrode diameter generated more aerosol particles, but lower ozone concentration when compared to larger electrode diameter. The differences in aerosol concentration due to the change of electric field strength decreased with increasing electrode diameter, because the mean kinetic energy was more uniform in the larger electrode. Electrode materials did not affect the I-V curve but the aerosol generation rate and the ozone concentration were clearly material-dependent. Gold was chosen as the discharge electrode because of stable and high sputtering yield.
Subjects
corona discharge
electric field strength
nanoparticle
louver
particle generator
SDGs

[SDGs]SDG7

[SDGs]SDG11

Type
thesis
File(s)
Loading...
Thumbnail Image
Name

ntu-101-D94841006-1.pdf

Size

23.32 KB

Format

Adobe PDF

Checksum

(MD5):70b4d797ca759bd05722803d6b3e3f89

臺大位居世界頂尖大學之列,為永久珍藏及向國際展現本校豐碩的研究成果及學術能量,圖書館整合機構典藏(NTUR)與學術庫(AH)不同功能平台,成為臺大學術典藏NTU scholars。期能整合研究能量、促進交流合作、保存學術產出、推廣研究成果。

To permanently archive and promote researcher profiles and scholarly works, Library integrates the services of “NTU Repository” with “Academic Hub” to form NTU Scholars.

總館學科館員 (Main Library)
醫學圖書館學科館員 (Medical Library)
社會科學院辜振甫紀念圖書館學科館員 (Social Sciences Library)

開放取用是從使用者角度提升資訊取用性的社會運動,應用在學術研究上是透過將研究著作公開供使用者自由取閱,以促進學術傳播及因應期刊訂購費用逐年攀升。同時可加速研究發展、提升研究影響力,NTU Scholars即為本校的開放取用典藏(OA Archive)平台。(點選深入了解OA)

  • 請確認所上傳的全文是原創的內容,若該文件包含部分內容的版權非匯入者所有,或由第三方贊助與合作完成,請確認該版權所有者及第三方同意提供此授權。
    Please represent that the submission is your original work, and that you have the right to grant the rights to upload.
  • 若欲上傳已出版的全文電子檔,可使用Open policy finder網站查詢,以確認出版單位之版權政策。
    Please use Open policy finder to find a summary of permissions that are normally given as part of each publisher's copyright transfer agreement.
  • 網站簡介 (Quickstart Guide)
  • 使用手冊 (Instruction Manual)
  • 線上預約服務 (Booking Service)
  • 方案一:臺灣大學計算機中心帳號登入
    (With C&INC Email Account)
  • 方案二:ORCID帳號登入 (With ORCID)
  • 方案一:定期更新ORCID者,以ID匯入 (Search for identifier (ORCID))
  • 方案二:自行建檔 (Default mode Submission)
  • 方案三:學科館員協助匯入 (Email worklist to subject librarians)

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science